Page 84 - Vol.05
P. 84
Off-site
On-site renewable renewable
energy energy Points
certificates
3% 25% 1
4.5% 37.5% 2
6% 50% 3
7.5% 62.5% 4
9% 75% 5
12% 100% 6
表三、給分表─依基地內外再生能源占建築
物總能源使用量的比例
5
LCGWP + LCODP × 10 ≤ 100
Calculation definitions for LCGWP + LCODP × 10 ≤ 100
5
LCODP = [ODPr × (Lr × Life + Mr) × Rc]/Life
82
January LCGWP = [GWPr × (Lr × Life + Mr) × Rc]/Life
2012
LCODP: Lifecycle Ozone Depletion Potenital (lbCFC11/Ton-Year)
LCGWP: Lifecycle Direct Global Warming Potential (lbCO 2 /Ton-Year)
GWPr: Global Warming Potential of Refrigerant (0 to 12,000 lbCO 2 /lbr)
JOURNAL
NEW FAB
ODPr: Ozone Depletion Potential of Refrigerant (0 to 0.2 lbCFC11/lbr)
TECHNOLOGY
Lr: Refrigerant Leakage Rate (0.5% to 2.0%; default of 2% unless otherwise demonstrated)
Mr: End-of-life Refrigerant Loss (2% to 10%; default of 10% unless otherwise demonstrated)
Rc: Refrigerant Charge (0.5 to 5.0 lbs of refrigerant per ton of gross ARI rated cooling
capacity)
Life: Equipment Life (10 years; default based on equipment type, unless otherwise
demonstrated)