Page 77 - Vol.19
P. 77
100
FLOW RATE VS.
DAMPER OPENING
90
PARALLEL BLADE ARRANGEMENT 80
ON-OFF
70
PERCENT OF FLOW RATE 50 PARALLEL
60
BLADES
OPPOSED BLADE ARRANGEMENT
MODULATING 40
BLADES
LOUVER DAMPER BLADE ARRANGEMENT DESIGN OPTIONS OPPOSED
30
20
Note: 10
This figure is typical, only. The relative blade open angle
versus percent of flow rate will vary with system pressure. 0
0 10 20 30 40 50 60 70 80 90
DEGREES OPEN
“L1” 200mm STD
“L2”
Type no. PFDCPA COUNTER WEIGHT
CENTER SUPPORT REQUIRED FOR
BLADES LONGER THAN 1200mm (”L1”)
SPECIFICATIONS
FRAME 200mm STANDARD LENGTH WITH
50mm FLANGES-3mm STAINLESS STEEL CENTER SUPPORT AS REQUIRED.
FLANGE MOUNTING HOLES (12×18 SLOT) EQUAL TO OR
LESS THAN 102 ON CENTER.
FAN INLET DAMPER BLADES-2.0mm STAINLESS STEEL.
FREQUENCY CONVERTER AXLES-20mm DIAMETER STAINLESS STEEL.
MOTORIZED SENSOR CHECK DAMPER LIQUID TIGHT SHAFT SEALS.
MANUAL ADJUSTABLE COUNTERWEIGHTS.
行
安 逆 風門開 作 力
力
力 安
安
造
NEW FAB ENGINEERING JOURNAL SEPTEMBER 2015 7 7