技術專文
圖 9、A1 測試結果(A 相降為 15%,持續 1 週期) 圖 10、A16 測試結果(三相降為 80%,持續 1 秒)
A1 Voltage Dip to 15% of U-nominal Phase A A16 Voltage Dip to 80% of U-nominal Phase A,B,C
ESS transfer to Online ESS transfer to Online
Phase A, 85% or greater dip, 1 cycle Phase A/B/C, 20% dip, 1S
Passed: ESS transfer to Online Mode Passed: ESS transfer to Online Mode
2016-10-17 10:20:55.535 S227: ENERGY SAVER SYSTEM OFF 60 (MCU) 2016-10-17 15:39:03.880 S227: ENERGY SAVER SYSTEM OFF 40 (MCU)
2016-10-17 10:20:55.640 S237: UPS NORMAL (MCU) 2016-10-17 15:39:04.000 S237: UPS NORMAL (MCU)
圖 11、B1 測試結果(三相輸入開路試驗) 圖 12、B2 測試結果(三相輸入短路試驗)
B1 AC Input Failure: 3 Phase Mains-Open Circuit Fault B2 AC Input Failure: 3 Phase Mains-Open Circuit Fault
Meets Dynamic Output Performance Classification 3 Meets Dynamic Output Performance Classification 3
Passed: ESS transfer to Online Mode Passed: ESS transfer to Online Mode
2016-10-17 15:55:03.710 S227: ENERGY SAVER SYSTEM OFF 20 (MCU) 2016-10-18 14:55:47.160 S227: ENERGY SAVER SYSTEM OFF 20 (MCU)
2016-10-17 15:55:03.780 S237: UPS NORMAL (MCU) 2016-10-18 14:55:47.280 S237: UPS NORMAL (MCU)
Group 之測試結果進行說明。 15%,持續時間 1 週期 (16.7ms), (Energy Saver System Off & UPS
其測試波形如 圖 9。 圖 9 上方波形 Normal)。由波形可看出 UPS 輸出
Group A 為 SEMI F47 的壓降測試
為輸入三相電壓(上方振幅較大波 電壓在一個週期內便回復穩定狀
項目,其中 A1 項目原本預定測試
形)、輸入三相電流(上方振幅較 態,對照輸入電壓仍有波動之情
的壓降條件為電壓降至 0%,持續
小波形)、輸出三相電壓(下方振 形,顯示 UPS 遇壓降從節能模式
時 間 1 週 期 (16.7ms), 如 圖4 中 幅較大波形)、輸出三相電流(下
切換至不斷電模式仍可降低壓降對
最左下角之綠點所示,但因模擬壓 方振幅較小波形),最下方之文字
於負載之衝擊。
降之測試設備在如此短暫的時間內 敘述為 UPS 之事件紀錄。從事件
只能將電壓降至約 15%,因此該 紀錄可看出該壓降條件使 UPS 由 圖 10 則為三相電壓降至 80%,持
測項之壓降條件便修正為電壓降至 節能模式成功切換至不斷電模式 續時間 1 秒之測試結果,該條件對