Page 47 - Vol.06
P. 47

100
                                                                                            Upper Bound

                                                                                              NJ= 2.7dB = 36%
                  10               Outdoor Footbridges                                             ǎ NJ
                                   Rhythmic Activities,
                Peak Acceleration (% Gravity)  1  Dining and Dancing  Log Velocity  Average, x
                                   Indoor Footbridges,
                                    Shopping Malls,
                                      Offices,
                                     Residences


                 0.1
                                                                             Lower Bound
                                   ISO Baseline Curve
                                  for RMS Acceleration
                                                                                      Log Stiffness
                                                                           Measured floor vibration data and Gordon Model
                 0.01
                    1            4            8            40
                                   Frequency, Hz
              Figure4. Acceptance criteria for human comfort        Figure5. Measured vibration data and Gordon model







              frequencies can be estimated from the fundamental natural         : axial shortening of column due to
              frequency equation of a uniformly loaded, simply-supported,       the weight supported
              beam:
                                                                           •  Design For Walking Excitation
                             when we consider a simple supported beam        When use equation (1) to calculate
                                                                           peak acceleration, since the floor system
              with uniform load, the midspan deflection of the beam is     is actually a two dimension system
                                                                           which consists of joist (or beam) and
                           , then the equation of natural frequency can
                                                                           girder mode, so we should consider the
                                                                           parameters   and   with (a) joist panel
              be rewritten as         For the combined mode, if both
                                                                           mode, (b) girder panel mode and (c)
              the beam or joist and girder are assumed simply supported,   combined panel mode.
                                                                             If the natural frequency of a floor
              using Dunkerley relationship       , the equation can be     is greater than 9-10 Hz, significant
                                                                           resonance with walking harmonics will
              rewritten as
                                                                           not occur, but walking vibration can
              where                                                        still be annoying. Experience indicates
                                                                           that a minimum stiffness of the floor to
                   :  beam or joist deflection due to the weight supported
                                                                           a concentrated load of 1 kN per mm (5.7
                   : girder deflection due to the weight supported
                                                                           kips per inch) is required for office and
                                                                           residential occupancies; the scanner used
                                                                           for semiconductor fabrication requires
                                 Constant Force   Damping Ratio   Acceleration Limit
                                                                           100 kN per mm, that is the difference of
                                    Pο         ß        аο/g × 100%
                                                                           soft and hard floor. The parameters of
               Offices, Residences,                                        equation (1) is listed in Table 2
               Churches            0.29 kN   0.02-0.05*   0.5%
               Shopping Malls      0.29 kN     0.02        1.5%
               Footbridges- Indoor  0.41 kN    0.01        1.5%            Example 1
               Footbridges- Outdoor  0.41 kN   0.01       5.0%               An outdoor footbridge of span 12m
               *0.02 for floors with few non-structural components (ceilings, ducts, partitions, etc.) as   with pinned supports and the cross-
               can occur in open work areas and churches
               0.03 for floors with non-structural components and furnishings, but with only small   section shown is to be evaluated for
               demountable partitions, typical of many modular office areas  walking vibration.
               0.05 for full height partitions between floors.
              Table 2. Recommended Values of Parameters and a 0  /g Limits




                                                                              NEW FAB TECHNOLOGY JOURNAL         APRIL 2012  47
   42   43   44   45   46   47   48   49   50   51   52