圖十六、水側最佳化節能運轉年度節能累計 ( 三廠 C/D-line Typical )
200 14
180
節能累計值(NT$/M) 12
160 每月節能費用(NT$/M/Month)
Enthlpy(焓)
140 10
120
8
100
6
80
60 4
40
2
20
0 0
Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec
Enthalpy
NT$ M/Yr.
表一、水側最佳化節能運轉效益驗證表 ( 三廠 C/D-line Typical )
Baseline Optimization
F3 Saving Saving
Optimization KWH KWH (KWH) (NT$K/Yr.)
(Before) (After)
Chillers 55,928,785 57,153,200 -1,224,415 -2,449
CWP 7,164,146 3,067,300 4,096,846 8,194
CHP 3,592,752 2,146,000 1,446,752 2,894
CT 2,630,362 1,838,400 791,962 1,584
SCHP 6,299,025 5,682,600 616,425 1,233
Total 75,615,069 69,887,500 5,727,569 11,455
作出相當之貢獻,另外此專案的執行 1996年8月。 Vol. 102, No.2, pp.679-940.
具有經濟與環保的雙重意義,進而 [5] 王啟川,冷卻水塔的熱流設 [9] Kirby P. Nelson, “Dynamics
建立綠色企業形象。 計,冷凍與空調,2001年10 of primary/secondary chilled
月,P .53-61。 water system,”ASHRAE
[6] 李永裕、許智凱、李文 Transactions, 1999, Vol.105,
興," Energy Conservation Part.2.
Analysis of Parallel Ice- [10] J. C. Dixon,Tires, Suspension
參考文獻 Storage Air-Conditioning and Handling, 2nd ed., SAE
System Operation Strategy " International, 1996.
[1] 「臺灣能源統計年報」,經濟 ,國立臺北科技大學。 [11] ASHRAE Handbook,“HVAC
部能源委員會。 [7] ASHRAE Handbook – Systems and Equipment,” Ch
[2] 最佳化冰機空調節能系統, Fundamentals, Chapter 33, 39, pp. 39.1-39.15, 2004.
EPSS。 1997.
[3] 柯明村,「通風節能技術上課 [8] Hartman, Tomas B., “Design
資料」,國立臺北科技大學,
issues of variable chilled-
台北,2003。
water flow through chillers,”
[4] 雷芳信,半導體廠冰水機節 ASHRAE Transactions, 1996,
能控制,中國冷凍空調雜誌,
46